Alarms, faults and system messages
9.5 List of alarms and faults
Number
Cause
A07910
Motor overtemperature
A07920
Torque/speed too low
A07921
Torque/speed too high
A07922
Torque/speed out of tolerance
F07923
Torque/speed too low
F07924
Torque/speed too high
A07927
DC braking active
F7966
Check commutation angle
F7969
Pole position identification incorrect An error has occurred during the pole position identification.
A07980
Rotary measurement activated
A07981
No enabling for rotary measure-
ment
A07991
Motor identification activated
F07995
Pole position identification unsuc-
cessful
F08501
Setpoint timeout
F08502
Monitoring time, sign-of-life expired •
F08510
Send configuration data not valid
A08511
Receive configuration data not
valid
A08526
No cyclic connection
A08565
Consistency error affecting adjust-
able parameters
A08800
PROFIenergy energy-saving mode
active
422
Remedy
Check the motor load.
Check the motor's ambient temperature.
Check the KTY84 or PT1000 sensor.
Check the overtemperatures of the thermal model (p0626 ... p0628).
The torque deviates from the torque/speed envelope curve.
Check the connection between the motor and the load.
Adapt the parameterization corresponding to the load.
Check the connection between the motor and the load.
Adapt the parameterization corresponding to the load.
Not required
Carry out pole position identification.
Check the following:
Motor connection
Motor data
Not required
Acknowledge pending faults.
Establish missing enables (see r00002, r0046).
Switch on the motor and identify the motor data.
An error has occurred during the pole position identification.
Check the following:
Motor connection
Motor data
Check the PROFINET connection.
Set the control into the RUN mode.
If the fault occurs repeatedly, check the monitoring time set p2044.
Check the PROFINET connection.
Check the PROFINET configuration
Activate the control with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
Check the following:
IP address, subnet mask or default gateway is not correct.
IP address or station name used twice in the network.
Station name contains invalid characters.
The PROFIenergy energy-saving mode is active.
The alarm automatically disappears when the energy-saving mode is
exited.