10.2.1.5

General data, PM240-2 - 600 V

Property
Line voltage
Output voltage
Input frequency
Output frequency
Power factor λ
Inrush current
Overvoltage category acc.
to EN 60664-1
Pulse frequency
Short-circuit current rating
(SCCR)
Electromagnetic compati-
bility according to IEC/EN
61800-3
Braking methods
Degree of protection ac-
cording to EN 60529
Ambient temperature
Ambient conditions accord-
ing to EN 60721-3-3
Temperature during stor-
age according to EN
60721-3-3
Cooling air
Relative humidity
Pollution according to EN
61800-5-1
Shocks and vibration ac-
cording to EN 60721-3-1
Installation altitude
Approvals
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Version
3 AC 500 V ... 690 V - 20 % ... +10 % (with fuses, Class J maximum 600 V)
3 AC 0 V ... 0.95 × input voltage (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 ... 550 Hz, depending on the control mode
> 0.9 line reactor not required
< LO base load input current
The inverter insulation is designed for surge voltages according to overvoltage Category III.
2 kHz (factory setting), can be adjusted to 4 kHz
If you increase the pulse frequency, the inverter reduces the maximum output current.
≤ 65 kA rms
Branch protection and short-circuit strength according to UL and IEC
(https://support.industry.siemens.com/cs/ww/en/view/109479152)
Devices with integrated filter are suitable for Category C2 environments.
DC braking, compound braking, dynamic braking with integrated braking chopper
IP20; must be installed in a control cabinet
LO base load power without derating:
HO base load power without derating:
LO/HO base load power with derating:
Restrictions for special ambient conditions (Page 469)
For the maximum permissible ambient temperature, also observe the permissible ambient
temperatures for the Control Unit and possibly operator panel (IOP or BOP-2) .
Protected against damaging chemical substance, according to environmental Class 3C3
-40 °C ... +70 °C
clean and dry air
< 95%
suitable for environments with degree of pollution 2, condensation not permissible
Long-term storage in the transport packaging according to Class 1M2
Transport in the transport packaging according to Class 2M3
Vibration in operation according to Class 3M2
without derating:
with derating:
Restrictions for special ambient conditions (Page 469)
cULus, CE, C-tick, SEMI F47, KCC,WEEE, RoHS, EAC
10.2 Technical data, Power Modules
-20 °C ... +40 °C
-20 °C ... +50 °C
-20 °C ... + 60° C
up to 1000 m above sea level
up to 4000 m above sea level
Technical data