6.5.1.1

Characteristics of U/f control

The inverter has different V/f characteristics.
Image 6-36
The inverter increases its output voltage to the maximum possible output voltage. The
maximum possible output voltage of the inverter depends on the line voltage.
When the maximum output voltage is reached, the inverter only increases the output
frequency. At this point, the motor enters the field weakening range: At constant torque, the
slip decreases quadratically as the speed increases.
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
The voltage boost of the characteristic optimizes the speed control at low speeds
With the flux current control (FCC), the inverter compensates for the voltage drop in the stator
resistor of the motor
Characteristics of V/f control
Advanced commissioning
6.5 Motor control
227