Siemens sinamics G120 Operating Instructions Manual page 306

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Advanced commissioning
6.7 Application-specific functions
Settings
Parameters
p2181
p2182
p2183
p2184
p2185
p2186
p2187
p2188
p2189
p2190
p2192
p2193 = 1
Speed deviation monitoring
Using this function, the inverter calculates and monitors the speed or velocity of a machine
component. The inverter analyzes an encoder signal, calculates a speed from the signal,
compares it to the motor speed and reports any excessive deviation between the encoder
signal and the motor speed.
Examples of how the function can be used:
● Gearbox monitoring for traction drives and hoisting gear
● Drive belt monitoring for fans and conveyor belts
● Blocking protection for conveyor belts
You require a transmitter for this function, e.g. a proximity switch. The inverter analyzes an
encoder signal at max. 32 kHz.
306
Description
Load monitoring response
Response when evaluating the load monitoring. Setting options
Table 6-46 Response options for load monitoring (Page 308)
Load monitoring speed threshold 1
Load monitoring speed threshold 2
Load monitoring speed threshold 3
Load monitoring torque threshold 1, upper
Load monitoring torque threshold 1, lower
Load monitoring torque threshold 2, upper
Load monitoring torque threshold 2, lower
Load monitoring torque threshold 3, upper
Load monitoring torque threshold 3, lower
Load monitoring delay time
Delay time for the message "Leave torque monitoring tolerance band"
Load monitoring configuration (factory setting: 1)
Table 6-45 Setting options for load monitoring (Page 304)
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Converter with CU250S-2 Control Unit

Advertisement

Table of Contents
loading

Table of Contents