A.3 Parameter
Table A- 12
How to change the inverter pulse frequency
Parameter
Description
p1800
Setting the inverter pulse frequency
The pulse frequency depends on the power unit.
Technical data, Power Modules (Page 432)
If you increase the pulse frequency, the inverter output current decreases (the maximum output current is
displayed in r0076).
If you use a sine-wave filter, you can only set the pulse frequency to values that are permissible for the
filter.
When operated with an output reactor, the pulse frequency is limited to a maximum of 4 kHz.