Siemens sinamics G120 Operating Instructions Manual page 69

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Depth with Control Unit and Operator Panel
• with Control Unit:
• With Control Unit and blanking cover / BOP-2:
• With Control Unit and IOP:
Table 4- 8
Frame size
FSC without/with filter
FSD without filter
FSD with filter
FSE without filter
FSE with filter
FSF without filter
FSF with filter
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Drilling dimensions, cooling clearances and fixing
Drilling dimensions (mm)
b
h
167
323
235
325
235
419
235
405
235
541
300
598
300
898
4.4 Installing Power Modules
Cooling air clearances (mm)
c
Top
Bottom
6
125
125
11
300
300
11
300
300
11
300
300
11
300
300
11
350
350
11
350
350
Installing
+ 62 mm
+ 73 mm
+ 84 mm
Mounting
Front
Screws/torque
(Nm)
65
4 x M5 / 3.0
65
4 x M6 / 6.0
65
4 x M6 / 6.0
65
4 x M6 / 10
65
4 x M6 / 10
65
4 x M8 / 13
65
4 x M8 / 13
69

Advertisement