6.8 Safe Torque Off (STO) safety function
Procedure with Startdrive
Proceed as follows to check as to whether the safety-related inputs are only used for the
safety functions:
1. Select the screen for the digital inputs.
2. Remove all digital input interconnections that you use as safety-related input F-DI:
3. You must delete the digital input connections for all CDS if you use the switchover of the
command data sets (CDS).
You can find a description of the CDS switchover in the operating instructions.
You have ensured that the safety-related inputs only control safety functions in the inverter.