Corrective maintenance
8.3 Firmware upgrade and downgrade
8.3.1
Upgrading firmware
When upgrading the firmware, you replace the inverter firmware by a later version. Only
update the firmware to a later version if you require the expanded functional scope of the
newer version.
Precondition
● The firmware version of your inverter is at least V4.5.
● Inverter and memory card have different firmware versions.
Procedure
Proceed as follows to upgrade the inverter firmware to a later version:
1.
2.
3.
4.
5.
394
Switch off the inverter power supply.
Wait until all LEDs on the inverter are dark.
Insert the card with the matching firmware into the in-
verter slot until it latches into place.
Switch on the inverter power supply again.
The inverter transfers the firmware from the memory
card into its memory.
The transfer takes approximately 5 ... 10 minutes.
While data is being transferred, the LED RDY on the
inverter stays red. The LED BF flashes orange with a
variable frequency.
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE