Installing
4.6 Installing Control Unit
Default setting 2: "Conveyor systems with Basic Safety"
DO 0: p0730, DO 1: p0731
Fixed speed setpoint 1: p1001, fixed speed setpoint 2: p1002, fixed speed setpoint active: r1024
Speed setpoint (main setpoint): p1070[0] = 1024
DI 0 and DI 1 = high: The inverter adds both fixed speed setpoints.
Designation in the BOP-2: coN SAFE
Default setting 3: "Conveyor technology with 4 fixed frequencies"
DO 0: p0730, DO 1: p0731
Fixed speed setpoint 1: p1001, ... fixed speed setpoint 4: p1004, fixed speed setpoint active: r1024
Speed setpoint (main setpoint): p1070[0] = 1024
Several DI 0, DI 1, DI 4 and DI 5 = high: The inverter adds the corresponding fixed speed setpoints.
Designation in the BOP-2: coN 4 SP
92
AO 0: p0771[0], AO 1: p0771[1]
AO 0: p0771[0], AO 1: p0771[1]
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
DI 0: r0722.0, ..., DI 5: r0722.5
DI 0: r0722.0, ..., DI 5: r0722.5
Converter with CU250S-2 Control Unit