Procedure with Startdrive
Proceed as follows to transfer settings from a memory card to the inverter:
1. Go online.
2. Select "Online & diagnostics".
3. Select "Backing up/reset".
4. Select the settings as shown in the diagram.
5. Start data transfer
6. Wait until Startdrive has signaled that the data transfer has been completed.
7. Go offline.
8. Switch off the inverter power supply.
9. Wait until all LEDs on the inverter are dark.
10.Switch on the inverter power supply again.
Your settings become effective after switching on.
You have now transferred your settings from a memory card to the inverter.
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Backing up data and series commissioning
7.1 Saving settings on a memory card