Extended messages

Overview
You must configure the "Extended messages" function module in order to be able to use the
extended messages.
Parameter
p2152
p2157
p2158
p2159
p2160
p2170
p2171
p2172
p2173
p2176
p2179
p2180
p2181
p2182
p2183
p2184
p2185
p2186
p2187
p2188
p2189
p2190
p2192
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Configuring a drive (Page 124)
Explanation
Delay for comparison n > n_max (Factory setting: 200 ms)
Speed threshold value 5 (Factory setting: 900 rpm)
Delay for n_act comparison with speed threshold value 5 (Factory setting: 10 ms)
Speed threshold value 6 (Factory setting: 900 rpm)
Delay for n_act comparison with speed threshold value 6 (Factory setting: 10 ms)
Current threshold value (Factory setting: 0 A)
Current threshold value reached delay time (Factory setting: 10 ms)
DC-link voltage threshold value (Factory setting: 800 V)
DC-link voltage comparison delay time (Factory setting: 10 ms)
Torque threshold value comparison delay time (Factory setting: 200 ms)
Output load detection current limit (Factory setting: 0 A)
Output load detection delay time (Factory setting: 2000 ms)
Load monitoring response (Factory setting: 0)
0: Load monitoring deactivated
1: A07920 for torque/speed too low
2: A07921 for torque/speed too high
3: A07922 for torque/speed out of tolerance
4: F07923 for torque/speed too low
5: F07924 for torque/speed too high
6: F07925 for torque/speed outside the tolerance
Load monitoring speed threshold 1 (Factory setting: 150 rpm)
Load monitoring speed threshold 2 (Factory setting: 900 rpm)
Load monitoring speed threshold 3 (Factory setting: 1500 rpm)
Load monitoring torque threshold 1 upper (Factory setting:
1000000 Nm)
Load monitoring torque threshold 1 lower (Factory setting: 0 Nm)
Load monitoring torque threshold 2 upper (Factory setting:
1000000 Nm)
Load monitoring torque threshold 2 lower (Factory setting: 0 Nm)
Load monitoring torque threshold 3 upper (Factory setting:
1000000 Nm)
Load monitoring torque threshold 3 lower (Factory setting: 0 Nm)
Load monitoring delay time (Factory setting: 10 s)
Advanced commissioning
6.7 Application-specific functions
Load moni-
toring (Page 304)