5.3.3.2
Standard Drive Control
Procedure for application class [1]: Standard Drive Control
2.
3.
4.
5.
6.
7.
8.
9.
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Select the required
function modules for
your application.
Select the I/O configuration to preassign the inverter interfaces.
Factory setting of the interfaces (Page 89)
Default setting of the interfaces (Page 91)
Set the applicable motor standard and the inverter supply voltage.
Select your motor.
If you use Startdrive, then this commissioning step is included in Step 5.
Enter the motor data according to the rating plate of your motor.
If you have selected a motor based on its article number, the data has
already been entered.
Set the most important parameters to suit your application.
Select the technological application:
• [0] Constant load: Typical applications include conveyor drives
• [1] Speed-dependent load: Typical applications include pumps and
fans
Motor identification:
• [1]: Recommended setting. Measure the motor data at standstill and
with the motor rotating. The inverter switches off the motor after the
motor data identification has been completed.
• [2]: Measure the motor data at standstill. The inverter switches off
the motor after the motor data identification has been completed.
Select this setting if the motor cannot freely rotate, e.g. for a
mechanically limited traversing range.
• [3]: Measure the motor data while it is rotating. The inverter switches
off the motor after the motor data identification has been completed.
• [11]: The same setting as [1]. The motor accelerates to the currently
set setpoint after the motor data identification.
• [12]: The same setting as [2]. The motor accelerates to the currently
set setpoint after the motor data identification.
Configure the encoder and complete the configuration (Page 132)
Commissioning
5.3 Quick commissioning with a PC.
127