Siemens sinamics G120 Operating Instructions Manual page 457

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Table 10- 31 PM240, IP20, frame sizes B, 3-phase 380 ... 480 VAC
Article no. - without filter
Article no. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to UL (from SIEMENS)
Fuse according to UL (Class J, K-1 or K-5)
Power loss
Required cooling air flow
Weight
Table 10- 32 PM240, IP20, frame sizes C, 3-phase 380 ... 480 VAC
Article no. - without filter
Article no. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to UL (from SIEMENS)
Fuse according to UL (Class J, K-1 or K-5)
Power loss
Required cooling air flow
Weight without filter
Weight with filter
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
6SL3224-...
...0BE22-2UA0
6SL3224-...
...0BE22-2AA0
2.2 kW
7.6 A
5.9 A
2.2 kW
7.6 A
5.9 A
3NE1813-0, 16 A
16 A
0.139 kW
24 l/s
4.3 kg
6SL3224-...
...0BE25-5UA0
6SL3224-...
...0BE25-5AA0
7.5 kW
21.9 A
5.5 kW
16.7 A
13.2 A
3NE1814-0, 20 A
0.240 kW
55 l/s
6.5 kg
10.2 Technical data, Power Modules
...0BE23-0UA0
...0BE23-0AA0
3 kW
10.2 A
7.7 A
3 kW
10.2 A
7.7 A
3NE1813-0, 16 A
16 A
0.158 kW
24 l/s
4.3 kg
...0BE27-5UA0
...0BE27-5AA0
11 kW
31.5 A
18 A
25 A
7.5 kW
23.7 A
19 A
3NE1814-0, 20 A
20 A
20 A
0.297 kW
55 l/s
6.5 kg
7 kg
7 kg
Technical data
...0BE24-0UA0
...0BE24-0AA0
4 kW
13.4 A
10.2 A
4 kW
13.4 A
10.2 A
3NE1814-0, 20 A
20 A
0.183 kW
24 l/s
4.3 kg
...0BE31-1UA0
...0BE31-1AA0
15 kW
39.4 A
32 A
11 kW
32.7 A
26 A
3NE1803-0, 35 A
35 A
0.396 kW
55 l/s
6.5 kg
7 kg
457

Advertisement

Table of Contents
loading

Table of Contents