Siemens sinamics G120 Operating Instructions Manual page 430

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Technical data
10.1 Technical data, CU250S-2 Control Unit
Feature
Operating temperature
Storage temperature
Relative humidity
Note
Short-term voltage dips in the external 24 V supply (≤ 3 ms and ≤ 95% of the rated voltage)
When the mains voltage of the inverter is switched off, the inverter responds to short-term
voltage dips in the external 24 V supply with fault F30074. Communication via fieldbus,
however, remains in effect in this case.
Permissible encoder cable lengths
Permissible cable lengths depend on the encoder type and the encoder cable.
Table 10- 1
TTL encoder
HTL encoder with bipolar signals (differential signals)
HTL encoder with unipolar signals
SSI encoder
DRIVE-CLiQ with MC800
DRIVE-CLiQ with MC500
We recommend that SIEMENS cables are connected using DRIVE-CLiQ components.
For SSI encoders, the permissible
cable length also depends on the
baud rate.
430
Data
-10° C ... 50° C
0° C ... 50° C
Observe any possible restrictions regarding the operating temperature as a result of
the Power Module.
- 40° C ... 70° C
< 95%
Maximum cable length:
Without inserted Operator Panel
With inserted BOP-2 or IOP Operator Panel
Condensation is not permissible.
100 m
300 m
100 m
100 m
50 m
100 m
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Converter with CU250S-2 Control Unit