Siemens sinamics G120 Operating Instructions Manual page 366

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Backing up data and series commissioning
7.3 Saving settings on an operator panel
BOP-2 → inverter
Procedure
To transfer the settings to the inverter, proceed as follows:
1.
2.
3.
4.
5.
6.
7.
You have transferred the settings to the inverter.
366
Go to the menu level "OPTIONS".
In the "OPTIONS" menu, select "FROM BOP".
Start data transfer with OK.
Wait until the inverter has written the settings to the memory card.
Switch off the inverter power supply.
Wait until all LEDs on the inverter are dark.
Switch on the inverter power supply again.
Your settings become effective after switching on.
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE