Installing
4.5 Connecting the line supply, motor, and inverter components
③
④
4.5.3
Connecting the inverter
Connecting the Power Module to the motor and power supply
Image 4-5
Connecting the PM240, PM240-2 and PM340 3AC Power Modules
Image 4-6
Connecting the PM240-2 and PM340 1AC Power Modules
76
The protective conductor for the connection of the PE busbar to the control cabinet housing must
have at least the same cross-section as the line supply cable of the machine or system (
For a cross-section of the line supply cable ≥ 6 mm², cross-section = 6 mm² suffices for the pro-
tective conductor.
The protective conductor must have at least the same cross-section as the motor cable of the
inverter.
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
①
Converter with CU250S-2 Control Unit
).