Siemens sinamics G120 Operating Instructions Manual page 412

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Alarms, faults and system messages
9.4 Faults
The fault buffer can accept up to eight actual faults. The next to last fault is overwritten if an
additional fault occurs after the eighth fault.
Image 9-7
Acknowledgement
You have multiple options to acknowledge a fault, e.g.:
● PROFIdrive control word 1, bit 7 (r2090.7)
● Acknowledge via the Operator Panel
● Switch-off the inverter power supply and switch-on again.
Faults detected during the inverter-internal monitoring of hardware and firmware can be
acknowledged only by switching the supply voltage off and on again. The list of faults in the
List Manual contains a note on this limited acknowledgement possibility.
Emptying the fault buffer: Fault history
The fault history can contain up to 56 faults.
The acknowledgement has no effect as long as none of the causes for the faults in the buffer
have been removed. If at least one of the faults in the fault buffer has been removed (the
cause of the fault has been removed) and you acknowledge the faults, then the following
happens:
1. The inverter accepts all faults from the fault buffer in the first eight memory locations of
the fault history (indexes 8 ... 15).
2. The inverter deletes the faults that have been removed from the fault buffer.
3. The inverter writes the time of acknowledgement of the faults that have been removed
into parameters r2136 and r2109 (fault time removed).
412
Complete fault buffer
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Converter with CU250S-2 Control Unit

Advertisement

Table of Contents
loading