Line Filter - Siemens sinamics G120 Operating Instructions Manual

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

3.4.2

Line filter

With a line filter, the inverter can achieve
a higher radio interference class. An ex-
ternal filter is not required for inverters
with integrated line filter.
Adjacent examples of line filters.
The line filter corresponds to Class A or B
according to EN55011: 2009.
NOTICE
The line filter is damaged when operated on inadmissible line supplies
The line filter is only suitable for operation on TN or TT line systems with a grounded
neutral point. The line filter is damaged if operated on all other line supplies.
• For inverters equipped with line filter, only connect to TN or TT line systems with a
External line filters for PM240
Power Module
FSA
FSF
GX
Power Module
FSA
FSB
FSC
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
grounded neutral point.
6SL3224-0BE13-7UA0,
6SL3224-0BE15-5UA0,
6SL3224-0BE17-5UA0,
6SL3224-0BE21-1UA0,
6SL3224-0BE21-5UA0
6SL3224-0BE38-8UA0,
6SL3224-0BE41-1UA0
6SL3224-0XE41-3UA0,
6SL3224-0XE41-6UA0
6SL3224-0XE42-0UA0
6SL3224-0BE13-7UA0,
6SL3224-0BE15-5UA0,
6SL3224-0BE17-5UA0,
6SL3224-0BE21-1UA0,
6SL3224-0BE21-5UA0
6SL3224-0BE22-2AA0,
6SL3224-0BE23-0AA0,
6SL3224-0BE24-0AA0
6SL3224-0BE25-5UA0,
6SL3224-0BE27-5UA0,
6SL3224-0BE31-1UA0
3.4 Components for the Power Modules
for PM240
FSA
Power
Line filter, class A
0.37 kW ... 1.5 kW
6SE6400-2FA00-6AD0
110 kW ... 132 kW
6SL3203-0BE32-5AA0
160 kW ... 200 kW
6SL3000-0BE34-4AA0
250 kW
6SL3000-0BE36-0AA0
Power
Line filter, class B
0.37 kW ... 1.5 kW
6SE6400-2FB00-6AD0
2.2 kW ... 4.0 kW
6SL3203-0BE21-6SA0
7.5 kW ... 15.0 kW
6SL3203-0BD23-8SA0
Description
for PM240 GX
35