Siemens sinamics G120 Operating Instructions Manual page 423

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Number
Cause
A13000
Licensing is not sufficient
F13010
Licensing is not sufficient
F13010
Licensing, function module not
licensed.
F13101
Know-how protection: Copy protec-
tion cannot be activated
F30001
Overcurrent
F30002
DC-link voltage overvoltage
F30003
DC-link voltage undervoltage
F30004
Inverter overtemperature
F30005
I2t inverter overload
F30011
Line phase failure
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Remedy
You are using functions that require a license, but you don't have the
appropriate licenses.
Activating licensed functions (Page 478)
Options requiring a license are used in the inverter, and the licensing is
not
sufficient.
At least one function module requiring a license is not licensed.
Deactivate the function module that is not licensed.
Insert a valid memory card.
Check the following:
Motor data, if required, carry out commissioning
Motor connection method (Υ / Δ)
V/f operation: Assignment of rated currents of motor and Power Mod-
ule
Line quality
Make sure that the line commutating reactor is connected properly
Power cable connections
Power cables for short-circuit or ground fault
Power cable length
Line phases
If this doesn't help:
V/f operation: Increase the acceleration ramp
Reduce the load
Replace the power unit
Increase the ramp-down time (p1121).
Set the rounding times (p1130, p1136).
Activate the DC-link voltage controller (p1240, p1280).
Check the line voltage (p0210).
Check the line phases.
Check the line voltage (p0210).
Check whether the inverter fan is running.
Check whether the ambient temperature is in the permissible range.
Check whether the motor is overloaded.
Reduce the pulse frequency.
Inverter temperature monitoring (Page 250)
Check the rated currents of the motor and Power Module.
Reduce current limit p0640.
When operating with V/f characteristic: Reduce p1341.
Inverter temperature monitoring (Page 250)
Check the input fuses of the inverter.
Check the motor feeder cables.
Alarms, faults and system messages
9.5 List of alarms and faults
423