Property
Environmental conditions during operation
Installation altitude
Restrictions for spe-
cial ambient conditions
(Page 469)
Climatic environmental
conditions
Mechanical environmental
conditions (shocks and
vibrations)
Protection against chemical
substances
Biological environmental
conditions
Cooling air
Contamination
Approvals
UL
, cUL
, CE, C-tick, SEMI F47
2)
2)
: Also observe the permissible ambient temperatures for the Control Unit and any Operator Panel (IOP or BOP-2).
1)
Use UL-certified fuses in order to satisfy the UL requirements.
2)
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Version
LO base load power 0.37 kW ... 132 kW:
•
HO base load power: 160 kW ... 250 kW:
•
HO base load power: 132 kW ... 200 kW:
•
Better than 3K3 according to EN 60721-3-3
Temperature range without derating
•
–
LO base load power 0.37 kW ... 250 kW:
–
HO base load power: 0.37 kW ... 110 kW:
–
HO base load power: 132 kW ... 200 kW:
Temperature range with derating
•
–
LO/HO base load power:
Restrictions for special ambient conditions (Page 469)
Relative humidity: 5 ... 95%, condensation not permitted
•
Oil mist, salt mist, ice formation, condensation, dripping water, spraying water, splashing
•
water and water jets are not permitted
The device is suitable for operation in mechanical environmental conditions that conform
with 3M1 according to EN 60721-3-3
Vibration test according to IEC 60068-2-6 with ten vibration cycles per axis
•
–
in the range 10 Hz ... 57Hz with a deflection of 0.075 mm
–
in the range 57 Hz ... 150Hz with an acceleration of 1 g
Shock resistance according to IEC 60068-2-27 with three impulses per axis in both direc-
•
tions
–
Peak acceleration: 5 g
–
Duration: 30 ms
protected against damaging chemical substances that conform with 3C2 according to EN
60721-3-3
suitable for operation in biological environmental conditions that conform with 3C2 according
to EN 60721-3-3
clean and dry air
suitable for environments with degree of pollution 2 according to EN 61800-5-1, condensa-
tion not permitted
10.2 Technical data, Power Modules
up to 1000 m above sea level
up to 2000 m above sea level
up to 4000 m above sea level
1)
-10° C ... +40° C
-10° C ... +50° C
-10° C ... +40° C
1)
-10° C ... +60° C
Technical data
455