Property
Environmental conditions during operation
Installation altitude
Restrictions for spe-
cial ambient conditions
(Page 469)
Climatic environmental
conditions
Mechanical environmental
conditions (shocks and
vibrations)
Protection against chemical
substances
Biological environmental
conditions
Cooling air
Contamination
Approvals
UL
, cUL
, CE, C-tick, SEMI F47
2)
2)
: Also observe the permissible ambient temperatures for the Control Unit and any Operator Panel (IOP or BOP-2).
1)
Use UL-certified fuses in order to satisfy the UL requirements.
2)
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Version
LO base load power 0.37 kW ... 132 kW:
HO base load power: 160 kW ... 250 kW:
HO base load power: 132 kW ... 200 kW:
Better than 3K3 according to EN 60721-3-3
Temperature range without derating
LO base load power 0.37 kW ... 250 kW:
HO base load power: 0.37 kW ... 110 kW:
HO base load power: 132 kW ... 200 kW:
Temperature range with derating
LO/HO base load power:
Restrictions for special ambient conditions (Page 469)
Relative humidity: 5 ... 95%, condensation not permitted
Oil mist, salt mist, ice formation, condensation, dripping water, spraying water, splashing
water and water jets are not permitted
The device is suitable for operation in mechanical environmental conditions that conform
with 3M1 according to EN 60721-3-3
Vibration test according to IEC 60068-2-6 with ten vibration cycles per axis
in the range 10 Hz ... 57Hz with a deflection of 0.075 mm
in the range 57 Hz ... 150Hz with an acceleration of 1 g
Shock resistance according to IEC 60068-2-27 with three impulses per axis in both direc-
tions
Peak acceleration: 5 g
Duration: 30 ms
protected against damaging chemical substances that conform with 3C2 according to EN
60721-3-3
suitable for operation in biological environmental conditions that conform with 3C2 according
to EN 60721-3-3
clean and dry air
suitable for environments with degree of pollution 2 according to EN 61800-5-1, condensa-
tion not permitted
10.2 Technical data, Power Modules
up to 1000 m above sea level
up to 2000 m above sea level
up to 4000 m above sea level
1)
-10° C ... +40° C
-10° C ... +50° C
-10° C ... +40° C
1)
-10° C ... +60° C
Technical data