For more information, please see the parameter list and the function block diagrams 2261 of
the List Manual.
Defining the function of an analog output - example
Advanced settings
You can manipulate the signal that you output via an analog output, as follows:
● Absolute-value generation of the signal (p0775)
● Signal inversion (p0782)
Additional information is provided in the parameter list of the List Manual.
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
To output the inverter output current via analog output 0, you
must interconnect AO 0 with the signal for the output current:
Set p0771 = 27.