Commissioning
5.3 Quick commissioning with a PC.
Procedure with Startdrive
Proceed as follows to adapt the encoder data:
1. Select the "Motor encoder" screen form.
2. Click the "Encoder data" button.
3. You have access to the following settings in the "Encoder data" screen form:
– You can change all of the encoder data.
– You can select another encoder type. In this screen form, STARTER only lists the
If you wish to set another encoder interface, you must reconfigure the inverter.
You have adapted the encoder data.
134
encoder types that are permitted for the configured interface.
Setting an absolute encoder (Page 498)