Alarms, faults and system messages
9.5 List of alarms and faults
Number
Cause
F30015
Motor cable phase failure
F30021
Ground fault
F30027
Time monitoring for DC-link pre-
charging
F30024
Overtemperature, thermal model
F30035
Overtemperature, intake air
F30036
Overtemperature, inside area
F30037
Rectifier overtemperature
A30049
Internal fan defective
F30059
Internal fan defective
A30502
DC-link overvoltage
A30920
Temperature sensor fault
A50001
PROFINET configuration error
A50010
PROFINET name of station invalid
A50020
PROFINET: Second control miss-
ing
For further information, please refer to the List Manual.
For further information, please refer to the List Manual.
424
Remedy
Check the motor cables.
Increase the ramp-up or ramp-down time (p1120).
Check the power cable connections.
Check the motor.
Check the current transformer.
Check the cables and contacts of the brake connection (a wire might
be broken).
Check the line voltage at the input terminals.
Check the line voltage setting (p0210).
Adapt the duty cycle.
Check whether the fan is running.
Check whether the ambient temperature is in the permissible range.
Check the motor load.
Reduce the pulse frequency.
Reduce the current of the DC current braking.
Check whether the fan is running.
Check the fan filter elements.
Check whether the ambient temperature is in the permissible range.
See F30035 and, in addition:
Check the motor load.
Check the line phases
Check the internal fan and if required replace.
Check the internal fan and if required replace.
Check the unit supply voltage (p0210).
Check the dimensioning of the line reactor.
Check that the sensor is connected correctly.
A PROFINET control is attempting to establish a connection with an in-
correct configuration telegram. Check to see whether "Shared Device" is
activated (p8929 = 2).
Correct name of station (p8920) and activate (p8925 = 2).
"Shared Device" is activated (p8929 = 2). However, only the connection
to a PROFINET control is available.
Overview of the manuals (Page 510)
Inverter temperature monitoring (Page 250)