Alarms, faults and system messages
9.5 List of alarms and faults
Number
Cause
F30015
Motor cable phase failure
F30021
Ground fault
F30027
Time monitoring for DC-link pre-
charging
F30024
Overtemperature, thermal model
F30035
Overtemperature, intake air
F30036
Overtemperature, inside area
F30037
Rectifier overtemperature
A30049
Internal fan defective
F30059
Internal fan defective
A30502
DC-link overvoltage
A30920
Temperature sensor fault
A50001
PROFINET configuration error
A50010
PROFINET name of station invalid
A50020
PROFINET: Second control miss-
ing
For further information, please refer to the List Manual.
For further information, please refer to the List Manual.
424
Remedy
Check the motor cables.
Increase the ramp-up or ramp-down time (p1120).
Check the power cable connections.
•
Check the motor.
•
Check the current transformer.
•
Check the cables and contacts of the brake connection (a wire might
•
be broken).
Check the line voltage at the input terminals.
Check the line voltage setting (p0210).
Adapt the duty cycle.
•
Check whether the fan is running.
•
Check whether the ambient temperature is in the permissible range.
•
Check the motor load.
•
Reduce the pulse frequency.
•
Reduce the current of the DC current braking.
•
Check whether the fan is running.
•
Check the fan filter elements.
•
Check whether the ambient temperature is in the permissible range.
•
See F30035 and, in addition:
Check the motor load.
•
Check the line phases
•
Check the internal fan and if required replace.
Check the internal fan and if required replace.
Check the unit supply voltage (p0210).
•
Check the dimensioning of the line reactor.
•
Check that the sensor is connected correctly.
A PROFINET control is attempting to establish a connection with an in-
correct configuration telegram. Check to see whether "Shared Device" is
activated (p8929 = 2).
Correct name of station (p8920) and activate (p8925 = 2).
"Shared Device" is activated (p8929 = 2). However, only the connection
to a PROFINET control is available.
Overview of the manuals (Page 510)
Inverter temperature monitoring (Page 250)
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Converter with CU250S-2 Control Unit