Property
Ambient conditions accord-
ing to EN 60721-3-3
Temperature during stor-
age according to EN
60721-3-3
Cooling air
Relative humidity
Pollution according to EN
61800-5-1
Shocks and vibration ac-
cording to EN 60721-3-1
Installation altitude
Approvals
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Version
FSA ... FSC:
Protected against damaging chemical substance, according to environmental
Class 3C2
FSD ... FSF
Protected against damaging chemical substance, according to environmental
Class 3C3
-40 °C ... +70 °C
clean and dry air
< 95%
suitable for environments with degree of pollution 2, condensation not permissible
Long-term storage in the transport packaging according to Class 1M2
Transport in the transport packaging according to Class 2M3
Vibration in operation according to Class 3M2
without derating:
with derating:
Restrictions for special ambient conditions (Page 469)
FSA ... FSC
cULus, CE, C-tick, KCC
FSD ... FSF
cULus, CE, C-tick, SEMI F47, KCC, WEEE, RoHS, EAC
10.2 Technical data, Power Modules
up to 1000 m above sea level
up to 4000 m above sea level
Technical data