Acceptance Tests For The Safety Functions; Recommended Acceptance Test - Siemens sinamics G120 Operating Instructions Manual

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Appendix
A.8 Acceptance tests for the safety functions
A.8

Acceptance tests for the safety functions

A.8.1

Recommended acceptance test

The following descriptions for the acceptance test are recommendations that illustrate the
principle of acceptance. You may deviate from these recommendations if you check the
following once you have completed commissioning:
● Correct assignment of the interfaces of each converter with the safety function:
– Fail-safe inputs
– PROFIsafe address
● Correct setting of the STO safety function.
Note
Perform the acceptance test with the maximum possible velocity and acceleration in
order to test the expected maximum braking distances and braking times.
Note
Non-critical alarms
The following alarms are issued following each system ramp-up and are not critical for
acceptance:
• A01697
• A01796
504
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Converter with CU250S-2 Control Unit