Changing the function of the terminals
The function of the terminals marked in color in the two diagrams above, can be set.
In order not to have to successively change terminal for terminal, several terminals can be
jointly set using default settings ("p0015 Macro drive unit").
The terminal settings made in the factory described above correspond to the following
default settings:
● Default setting 12 (p0015 = 12): "Standard I/O with analog setpoint"
● Default setting 7 (p0015 = 7): "Fieldbus with data set switchover"
4.6.6

Default setting of the interfaces

Default setting 1: "Conveyor technology with 2 fixed frequencies"
DO 0: p0730, DO 1: p0731
Fixed speed setpoint 3: p1003, fixed speed setpoint 4: p1004, fixed speed setpoint active: r1024
Speed setpoint (main setpoint): p1070[0] = 1024
DI 4 and DI 5 = high: The inverter adds both fixed speed setpoints
Designation in the BOP-2: coN 2 SP
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
AO 0: p0771[0], AO 1: p0771[1]
Installing
4.6 Installing Control Unit
DI 0: r0722.0, ..., DI 5: r0722.5
91