NOTE!
For further information on the parameters mentioned above, refer to item 3.
2.2.4
Access of the Parameter – Acyclic Messages
The PROFIBUS-05 communication kit allows parameter reading/writing services by means of DP-V1 acyclic
functions. The parameter mapping is done based on the slot and index addressing, as showed in the formula
below:
Slot:
(parameter number - 1) / 255.
Index: (parameter number - 1) MOD 255.
NOTE: MOD represents the remainder of the integer division.
2.3

ETHERNET/IP

2.3.1

ETHERNETIP-05 and ETHERNET-2P-05 Accessory

Connector

The EtherNet/IP communication module has a standard female RJ45 connector (T-568A or T-568B).

Indications

EtherNet/IP defines two LEDs for status indication: one for the communication module (MS) and another for the
network (NS).
The MS LED indicates the conditions of the module itself. That is, whether it is able to work or not. The table
below shows the possible states:
LED Status
Off
Without power supply
Green
Module controlled by a scanner in RUN mode.
Flashing green
Not configured or scanner in IDLE mode
Red
Major fault
Flashing red
Recoverable fault
Flashing green/red
Equipment performing self-diagnosis
The NS LED indicates the conditions of the EtherNet/IP network.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Ethernet-05 part number: 10933688 (1 Ethernet port).
Ethernet-2P-05 part number: 12272760 (2 Ethernet ports with
integrated switch).
Composed by the Anybus ABCC-EIP communication module,
mounting instructions and a "torx" screw driver for fixing the
module.
Standard RJ45 connector.
ODVA certified interface.
Table 2.11: State of the EtherNet/IP module
Description
Comments
-
In this state, data exchange effectively occurs.
In this stage there is no cyclic data communication
with the scanner, or the scanner is in IDLE mode.
Internal error of the module. Equipment must be
reinitialized.
Internal error of the module, but the return to the
normal state occurs automatically after the cause of
the fault is corrected.
It occurs during initialization.