V/F Current Limitation [26] - WEG CFW-11 Programming Manual

Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

The function is activated with P0202=2 (Adjustable V/f).
The factory setting of P0144 (8.0 %) is adequate for standard motors with rated frequency of 60 Hz. When using
a motor with rated frequency (adjusted in P0403) different from 60 Hz, the default value for P0144 may become
inadequate, being able to cause difficulties in the motor starting. A good approximation for the setting of P0144 is
given by the formula:
If it is necessary to increase the starting torque, increase gradually the value of P0144.
Output
Voltage
100 %
P0142
P0143
P0144

9.3 V/f CURRENT LIMITATION [26]

P0135 – Maximum Output Current
Adjustable
0.2 to 2xI
Range:
Properties:
V/f and VVW
Access groups
01 PARAMETER GROUPS
via HMI:
P0344 – Current Limitation Configuration
Adjustable
0=Hold -FL ON
Range:
1=Decel. -FL ON
2=Hold -FL OFF
3=Decel. -FL OFF
Properties:
V/f, CFG and VVW
Access groups
01 PARAMETER GROUPS
via HMI:
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
P0144 =
Line rated voltage
0.1 Hz
3 Hz
P0146
Figure 9.8 - V/f curve in function of P0142 to P0146
nom-HD
26 V/f Current Limit
26 V/f Current Limit
3
x P0142
P0403
Speed/Frequency
P0134
P0145
Scalar Control (V/f)
P0202=2
Factory
1.5xI
nom-HD
Setting:
Factory
1
Setting:
9
9-7