Auxiliary Alarm Signaling Equipment; Figure 12-4: 5140Led Indicator Module - ADEMCO VISTA-32FB Installation And Setup Manual

Fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

If used, program field 3 20 must be set to 2, and the 5140LED Module must be connected to
J2/OUT 1, 3, 4, 5 as shown in the diagram below. It is designed to be mounted into a
standard single-gang electrical box and installed as follows:
1. Pull wires from the panel's J2 connector through an opening in the single-gang box and
splice these wires to the module's flying leads. Solderless splices may be used.
2. Mount the module's PC board onto one side of the PC board retainer bracket (supplied).
3. Slide the PC board retainer bracket into the box and fasten with screws (supplied).
4. Mount the stainless steel decorative cover (supplied) onto the box.

Auxiliary Alarm Signaling Equipment

The J2 connector can be used to provide triggers for the following conditions:
Fire alarm.
Burglary/audible panic alarm.
Silent panic/duress alarm.
Fire supervisory.
Trouble.
Opening/closing (arming/disarming).
These triggers may be used to trip auxiliary alarm signaling equipment such as ADEMCO's
7720, 7720ULF, and 7920SE Long Range Radios, 7820 Transmitter (when set to the zone
mode), and 7835 Tranceiver (when set to the zone mode). Note that not all of these triggers
are available for all settings of field 3 20. See Figure 12-1 J2 Pin Assignments and Functions
shown earlier for configuration of the J2 triggers.
The open/close, fire alarm, fire supervisory, burglary/audible panic alarm, silent panic/duress
alarm, and trouble triggers are common to all partitions and must be enabled for each
partition (data field 2 20). The open/close trigger is LOW when all enabled partitions are
OFF if normal.
1

Figure 12-4: 5140LED Indicator Module

J2 CONNECTOR
2
3
4
5
6
7
8
9
4142TR CABLE WIRES COLORS
4142TR CABLE
AC POWER
BROWN
DIALER 2 FAULT
GREEN
COMM FAILURE
ORANGE
DIALER 1 FAULT
YELLOW
BLUE
(TO TERM
RED
+
TO AUX PWR 1
RED
OUTPUT
(TO TERM
BLACK
BLACK
5140LED MODULE
WIRES COLORS
Section 12 – J2 Trigger Outputs
5140LED MODULE
AC POWER
COMM FAILURE
DIALER 1 FAULT
DIALER 2 FAULT
FUTURE USE
12–5