Other System Messages
COMM. FAILURE at the keypad indicates that a failure occurred in the telephone
communication portion of your system.
LO BAT and a zone descriptor, accompanied by a once-per-minute beep at the keypad,
indicates that a low battery condition exists in the wireless transmitter displayed. Press
any key to silence the audible warning sound.
SYSTEM LO BAT at the keypad indicates that a low battery condition exists with the
system's backup battery.
HSENS and a zone number indicates a smoke detector with a high sensitivity level,
which may cause false alarms. The detector is dirty and should be cleaned or replaced.
LSENS and a zone number indicates a smoke detector with a low sensitivity level.
Detectors with a low sensitivity might not detect a smoke condition. The detector should
be cleaned or replaced.
RCVR SET UP ERROR at the keypad indicates that the system has more wireless zones
programmed than the wireless receiver can support. If this is not corrected, none of the
zones in the system will be protected. If additional wireless zones are desired, use an
appropriate receiver.
MODEM COMM at the keypad indicates that the control is on-line with a remote
computer.
System Off-Normal Report
If programmed, a unique Off-Normal report will be generated instead of the periodic test
report if any of the following conditions are present at the time of the report:
Fire trouble on any zone (zone response types 9, 16, 17, 18).
Fire supervisory present (zone response type 18).
Unrestored fire alarm on any zone.
Bypass of any fire zone.
Bell circuit fault for any supervised fire bell.
Bypass/disable of any supervised fire bell.
Telco fault of either dialer line.
Bypass/disable of either dialer.
Earth ground fault present.
Bypass of earth ground supervisory zone.
Fault on LORRA XMIT OK signal (if enabled).
LORRA trigger bypassed.
AC failure.
Low system battery.
Keypad supervision fault.
This report will be sent as follows:
Contact ID: Code 608
High Speed: Channel 3 of system report used (channel 9 = 6)
Low Speed:
Digits programmed in System Group #4 report codes (Report Code
Programming in #93 Menu Mode of the Quick Start Guide).