Ul609 Grade A Local Mercantile Premises/Local Mercantile Safe And Vault; Ul365 Police Station Connected Burglar Alarm; Ul611/Ul1610 Central Station Burglary Alarm - ADEMCO VISTA-32FB Installation And Setup Manual

Fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

VISTA-32FB Installation and Set-Up Guide
When the dialer is used, program it to send fire alarm, fire supervisory (if used), trouble,
AC loss, low battery, normal dialer test, and off-normal dialer test reports. Field
must be set to 024 maximum so that test reports are sent at least once every 24 hours.
If a secondary number is programmed, set the maximum number of dialer re-tries to 3, 4,
or 5 in field 3 21.

UL609 Grade A Local Mercantile Premises/Local Mercantile Safe and Vault

All zones must be configured for EOLR supervision ( 41=0). Wireless sensors may not
be used. If 4190WH RPMs are used, set field 24 to 0 to enable tamper detection.
Attach a door tamper switch (supplied) to the VISTA-32FB cabinet backbox. For safe and
vault installations, a back box tamper switch (not supplied) must also be attached to the
backbox. (Also see Mounting the Cabinet in Section 4: Installing the Control)
Wire an ADEMCO AB12 Grade A Bell/Box to the bell output. Bell wires must be run in
conduit. Program the bell output for 16 or longer timeout and for confirmation of arming
ding. (Also see Section 14: External Sounders).
Wire the VISTA-32FB tamper switch and AB12 Bell/Box tamper switches to any EOLR-
supervised zone (zones 1-8). Program this zone for day trouble/night alarm (type 05) or
24-hour audible alarm (type 07) response. The 24-hour alarm response must be used for
multiple partitioned systems.
Entry delays must not exceed 45 seconds, and exit delays must not exceed 60 seconds.

UL365 Police Station Connected Burglar Alarm

Follow the instructions for UL609 local installations given above.
For Grade A Service:
You may use the VISTA-32FB dialer alone, or the 7720 Long Range Radio alone.
When using the dialer, program it to send Burglary Alarm, Low Battery, and
Communicator Test reports. Field 27 must be set to 024 (or less) so that test reports
are sent at least once every 24 hours.
If using the 7720, connect it to the VISTA-32FB burglary/audible panic alarm trigger.
For Grade AA Service:
You must use a 7920SE Long Range Radio.
Connect the 7920SE to the VISTA-32FB burglary/audible panic alarm trigger.

UL611/UL1610 Central Station Burglary Alarm

Follow the instructions for UL609 local installations given above.
For Grade A Service:
You must use the VISTA-32FBs dialer with a 7720 Long Range Radio.
Connect the control's burglary/audible panic alarm trigger (on J2 header) to the 7720.
Program a 24-hour trouble response for Zone 974 to enable main dialer supervision. The
VISTA-32FB will activate the burglary/audible panic trigger when a corresponding alarm
is detected, and will activate the trouble trigger when a main dialer fault is detected.
Also connect the 7720s radio fault output to one of the VISTA-32FBs EOLR-supervised
zones (i.e., 1-8). Program this zone for a trouble by day/alarm by night (type 05) or a 24-
hour alarm (type 07, 08) response to radio faults.
A–2