With Alarms Present
A momentary short across zone 7 will silence alarm bell and keypad sounds, and will disarm
the partition if it was armed. The keyswitch LEDs provide a memory of alarm indication (see
table below). A subsequent short across zone 7 will clear the alarm memory indication and
reset 2-wire smoke and glassbreak detectors (if used).
When field 15 is set to 9, the keyswitch operates as follows:
A momentary short across zone 7 will silence alarm bell sounds (i.e., turn off Bell 1, Bell 2
and the auxiliary relay if programmed for alarms) only if a fire alarm is present. Outputs
will re-sound automatically if a new fire alarm condition is detected. Burglary alarms will
not trigger the bell output until a [User Code] + [OFF] is entered at the keypad. A
momentary short has no effect if there are no fire alarms present. This mode is used to
provide the fire department with keyswitch silence capability without compromising the
burglary system's security.
Open/Close reporting for the keyswitch is enabled in field 40, and the keyswitch reports as User
0.

5140LED Indicator Module

An optional 5140LED Indicator Module can be used in municipalities that require dedicated
indicators for communicator fault status. The 5140LED provides the following indicators:
1. AC POWER:
• ON if AC power is present.
• OFF if AC power is not present.
2. COMM FAILURE:
• ON if the maximum number of attempts were made (field 3 21) to transmit a
• OFF if normal.
3. DIALER 1 FAULT:
4. DIALER 2 FAULT:
12–4
LED indications are defined as follows:
GREEN
RED
OFF
OFF
ON
OFF
OFF
ON STEADY
OFF
SLOW FLASH
OFF
RAPID FLASH
message to the central station. Enter [User Code] + [OFF] following a successful
transmission to turn off.
ON if the main dialer line is faulted. Correct the problem, and then enter [User
Code] + [OFF] to turn off.
OFF if normal.
ON if the backup dialer line is faulted. Correct the problem, and then enter [User
Code] + [OFF] to turn off.
MEANING
DISARMED and NOT READY
DISARMED and READY
ARMED AWAY
ARMED STAY
ALARM MEMORY