Entry Errors

If an invalid address is entered, the keypad will display FC.
If a program entry is improperly entered (for example, a number larger than permitted),
the entry position of the keypad display will go blank.
In either of the above cases, simply re-enter [ ] + [the correct field number] and
enter the correct data.

Programming System-Wide Data Fields

Values for some programming fields are system-wide (global), and some can be different for
each partition (partition-specific). Note that the partition-specific programming fields are
automatically skipped when programming the global fields. If the system has only 1
partition, the partition-specific fields will not be automatically skipped. To program
system-wide data fields, do the following:
1. Enter Program Mode: [Installer code] + [8 0 0]. After the Program Mode has been
entered, the following will be displayed:
2. If the control has not been programmed before, enter 97 to load factory defaults.
3. Press [ ] and enter the first field number to be programmed (for example, 00,
Installer's Code). Make the desired entry. When the field is complete, the keypad will
beep three times and will advance to the next field. Enter the desired change or press
[ ] and enter the next field number to be programmed.
4. If the number of digits entered in a data field is less than the maximum permitted (for
example, a phone number), the keypad displays the last entry and waits. To proceed,
enter [ ] + [the next data field to be programmed] (e. g., press 08).
Partition-specific programming fields are skipped unless entered specifically or the
system is set up for 1 partition only. To change to the next page of fields, press 94. To
return to the previous page of fields, press 99.

Programming Partition-Specific Data Fields

To program partition-specific data fields once in Program Mode, do the following:
1. Press 91, which prompts for the partition number desired.
SUMMARY OF DATA FIELD PROGRAMMING COMMANDS
Select partition for programming partition-specific fields
91
Display the software revision level of the control panel
92
Enter Menu Mode Programming
93
Go to next page of fields
94
Go back to previous page of fields or exit Programming Mode with
99
no Installer Code lockout
Exit Programming Mode with Installer Code lockout
98
press 99 or 98 to exit Program Mode
Section 20 – The Mechanics of Programming
Program Mode
Fill # View -00
First Page of fields
( 00- 90)