VISTA-32FB Installation and Set-Up Guide

Fire Drill Test ([code] + [#69])

This test causes fire bells (or any bell having a non-zero response type in the #93 Menu
Mode) to be activated (in either steady or pulsing manner, as programmed in field 3 15) for
the purpose of conducting a fire drill or a bell test. This test can only be activated by the
installer or a master user from Partition 1 keypads by entering the corresponding security
code and pressing [#69] while the burglary portion of the system is disarmed. Keypads
display FIRE DRILL ACTIVE while this test is active. Entering any security code and
pressing OFF stops the test. Note that the system continues to monitor all 24-hour zones
(fire, panic, etc.) while this test is active, and will end the test when an alarm condition is
detected. This test should be conducted at periodic intervals, as determined by the local
authority having jurisdiction.

One-Man Fire Walk-Test ([code] + [#68])

This test causes the system to sound console beeps and bell dings in response to fire zone
faults (zone type 9, 16 and 17) for the purpose of allowing proper zone operation to be
checked without triggering alarms. Note that the system will not be operational as an alarm
system (i.e., cannot sense alarms) while this test is active. The test can only be activated by
the installer by entering the Installer's Code and pressing [#68] while the burglary portion of
the system is disarmed. This test should be conducted at periodic intervals, as determined by
the local authority having jurisdiction.
When this test is first activated, the system will display:
USE BELL DING?
0 = NO 1 = YES
AUTO-TEST DET?
0 = NO
For true detector sensitivity tests, and for compliance with fire codes, 0 (NO) must be
entered at the AUTO-TEST DET? prompt.
LOG RESULTS?
0 = NO 1 = YES
30–2
Enter 1 (YES) to have the fire bells associated with each
point sound for 3 seconds when a point is faulted.
Enter 0 (NO) if only keypad sounders are desired.
The next prompt will be displayed.
Enter 1 (YES) to have the system automatically test all
polling loop points with a fire response type 9 or 16. Other
1 = YES
fire zones will have to be tested manually.
Enter 0 (NO) to test every point manually.
The next prompt will be displayed.
Enter 1 (YES) to have the system log each point as it is
tested. A list of untested points will also be logged.
Enter 0 (NO) if you do not want the system to keep track
of the results.
The next prompt will only be displayed if Contact ID report
format has been selected.