VISTA-32FB Installation and Set-Up Guide
7–4
Notes: - Do not use the 4197 module.
- Refer to 4297 instructions for more detailed installation information.
The limits shown below supercede the limits described in the 4297 instructions.
- Do not connect 4297 modules in series.
CONTROL
PANEL
Input Loop Limits:
- 128mA max. No more than 64mA
on any individual wire run.
- No individual wire run may exceed:
Gauge
Length
#22
650 ft.
#20
950 ft.
#18
1500 ft.
#16
2400 ft.
- Total length of all wire runs combined cannot
exceed 4000 ft. (2000 ft. if using unshielded
wire in conduit or shielded wire).

Figure 7-2a: Polling Loop Connections Using One 4297 Extender Module

Notes:
- Do not use 4197 module.
- Refer to 4297 instructions for more detailed installation information.
The limits shown below supercede the limits described in the 4297 instructions.
- Do not connect 4297 modules in series.
CONTROL
PANEL

Figure 7-2b: Polling Loop Connections Using Multiple Extender Modules

Input Polling Loop
4297
- - -
RPM
RPM
MODULE
Extension Loop Limits:
- Same as for the input polling loop.
Combined Input and Extension Polling Loop Limits:
- No more than 120 devices combined.
- Total length of all wire runs on all loops combined can-
not exceed 6400 ft. (3200 ft. if using unshielded wire in
conduit or shielded wire).
4297
Input Polling
Loop
4297
4297
Up to 8 modules may be connected
in parallel. Extension loops will be
electrically isolated if blue jumper
on each 4297 is left intact.
Combined Input and Extension Loop Limits:
- No more than 120 devices combined on all loops.
- To calculate the maximum wire run allowed on each extension loop:
1. Determine the total wire length of all input loops combined.
2. Subtract this number from 6400 ft. (3200 ft. for shielded cable or
unshielded cable in conduit).
The result is the maximum wire run length for each extension loop.
Extension Polling Loop
- - -
RPM
RPM
Extension Loop #1
- - -
RPM
RPM
Extension Loop #2
- - -
RPM
RPM
Extension Loop #8
- - -
RPM
RPM
Extension Loop Limits:
Each individual loop has the
same limits as the input loop.