83 FIRST TEST REPORT TIME
Enter the day (00-07) and time (00-23 hours/00-59 min.) that the first Test report shall
be transmitted.
Enter 00 in all locations if the Test report is to be sent immediately upon exiting.
Enter 00 in the day location if the report is to be sent at the next occurrence of the time
that is set.
Note: Day 01=Monday. See Report Code Programming (System Group 1) in #93 Menu
Mode Programming section of the Quick Start Guide for assigning the Test Report Code.
84 SWINGER SUPPRESSION (partition-specific)
This option limits the number of messages (alarms or troubles) sent for a specific
channel in an armed period (Swinger Suppression). Enter 01-15. If 00 is selected, all
alarm or trouble codes are reported.
Must be 00 (disabled) for commercial fire and UL installations.
85 ENABLE DIALER REPORTS FOR PANICS and DURESS [0000]
(partition-specific)
Enter 1 for each panic/duress for which reporting is desired.
Note: To enable Duress reporting a non-zero report code must be assigned to Zone 992
(duress) in Zone Programming in #93 Menu Mode Programming section of the Quick
Start Guide.
87 ENTRY WARNING (partition-specific)
Enter 0 for 3 short beeps, or 1 for slow beeps that continue for the entire entry delay
period.
88 BURG. ALARM COMM. DELAY (partition-specific)
Enter 0 for no delay on burglary alarm communication. Enter 1 for 16-second delay (no
delay on 24-hour reports). Must be 0 for UL installations.
89 RESTORE REPORT TIMING
Enter 0 for instant Restore report as zone restores.
Enter 1 for reporting after bell timeout if zone restored. Enter 2 for Restore report
when system is subsequently disarmed. Must be 2 for commercial fire or UL
commercial burglary installation.
90 SECONDARY SUBSCRIBER ACCT #
(partition-specific)
Enter the 3- or 4-digit number (depending on report format) for the secondary
subscriber account: 00-09; B-F (11-15). Each number requires a 2-digit entry to allow
entry of hexadecimal digits (B-F). If a 3-digit number is to be used, enter data only in
the first 6 locations, leaving the last two unfilled. Default is [15 15 15 15]. Erase the
field by entering 90 .
Note: This field must be programmed if a secondary phone number is used (field
This account number can be the same as the primary account number.
23–10
[00, 12, 00]
Enter 00-09; B-F (11-15)
|
|
[03]
995
996
999
|
|
|
[15
15
15
|
|
Duress
[1]
[0]
[0]
|
15]
34).