In This Section
General Information
Remote Keypad Sounder Operation and Wiring
Remote Keyswitch Operation and Wiring
5140LED Indicator Module
Auxiliary Alarm Signaling Equipment
Event Log Printer Connections
Direct-Wire Downloading
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
General Information
The J2 connector, located in the upper right-hand corner of the main PCB, provides 1 input
(labeled INPUT 1) and seven trigger outputs (labeled OUT 1 - OUT 7) that can be used to
interface to the following:
•
Remote keypad sounder.
•
UL Listed keyswitch.
•
5140LED Indicator Module.
•
Auxiliary alarm signaling equipment such as an ADEMCO Long Range Subscriber
Radio.
•
Event logging serial printer (via the 4100SM Interface Module).
•
PC computer used to direct-wire download the panel's programming information (via the
4100SM Interface Module).
The trigger output ratings are listed below. Note that all outputs are power-limited.
The pin assignments for the J2 connector are shown in Figure 12-1. Use a 4142TR 9-wire
trigger cable (one is supplied) to interface with this connector. The panel does not supervise
field wiring connected to this connector.
Program fields 3 19 and 3 20 are used to select the functions of INPUT 1 and OUT 1-7 as
indicated in Figure 12-1.
When using J2 for LORRA, Input 1 (Pin 9) is supervised by Zone 973, which is used for
supervision of the LORRA XMIT OKAY signal. Assign a 24-hr. zone response type (5 or 19) to
this zone.
Outputs 1, 5, 7:
Remaining Outputs:
J2 Trigger Outputs
LOW:
2K to ground
HIGH: 10-14 VDC @ 20 mA max
LOW:
1K to ground
HIGH: 10-14 VDC through 5K
S E C T I O N
1 2