Vista-32Fb Summary Of Connections - ADEMCO VISTA-32FB Installation And Setup Manual

Fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

WARNING: OWNER'S INSTRUCTION NOTICE NOT TO BE REMOVED
REFER TO INSTRUCTIONS K3521 FOR ADDITIONAL INFORMATION
THIS EQUIPMENT
SHOULD BE INSTALLED
IN ACCORDANCE WITH
THE NATIONAL FIRE
PROTECTION ASSOC-
NOTE: As shipped,
IATION'S STANDARD 72
(NATIONAL FIRE
Vista-32FB is suitable
PROTECTION ASSOC.,
for UL Commercial Fire
BATTERYMARCH PARK,
Installations. Cabinet
QUINCY, MA. 02269).
PRINTED INFORMATION
supports up to 14AH
DESCRIBING PROPER
Batteries. Use Vista-ULKT
INSTALLATION,
Cabinet Kit to house
OPERATION, TESTING,
MAINTENANCE AND
up to 34.4AH Batteries.
REPAIR SERVICE IS
Also use this kit along
TO BE PROVIDED WITH
with 1451 Transformer
THIS EQUIPMENT.
for UL Listed Commercial
Burglary Installations.
BATTERY TABS
BLK
Connect to 12V, 7AH min/34.4AH max
lead acid batteries using cables supplied.
See instructions for required capacity.
Float charging voltage: 13.7VDC. Battery
normally need not be replaced for
at least 3 yrs.
OPTIONAL REMOVABLE
TERMINAL BLOCK KIT:
ADEMCO NO. 4142BLK
2A Circuit
Breaker
TRANSFORMER
W/ENCLOSURE
(lower left corner of cabinet)
REPLACE COVER AFTER
INPUT:
BLACK
BL
120VAC, 60HZ,
1.0A max.
BL
WHITE
Connect to a
dedicated circuit.
Connect to
Connect to
Earth Ground
Proper Earth
Terminal 30
GRN
GRN
Ground. See
instructions.
NOTES
NOTE 1:
The combined standby current
drawn from aux pwr #1, aux pwr #2
and polling loop cannot exceed
1.0A.The combined alarm current
drawn from aux pwr #1, aux
pwr #2, polling loop, bell 1 and
bell 2 cannot exceed 2.3A.
NOTE 2:
2k EOLR is Ademco model 610-7
NOTE 3:
Assembled In
See instructions on setting
Mexico
addresses & for max # of keypads
and wire run length restrictions.
Keypad color subject to approval
of local authority.
WARNING:
THIS UNIT MAY BE PROGRAMMED TO
INCLUDE AN ALARM VERIFICATION
FEATURE THAT WILL RESULT IN A DELAY
OF THE SYSTEM ALARM SIGNAL FROM
THE INDICATED FIRE CIRCUITS. THE
TOTAL DELAY (CONTROL UNIT PLUS
SMOKE DETECTORS) SHALL NOT EXCEED
60 SECONDS. NO OTHER INITIATING
DEVICES SHALL BE CONNECTED TO
THESE CIRCUITS UNLESS APPROVED BY
THE LOCAL AUTHORITY HAVING
JURISDICTION.
CONTROL UNIT
SMOKE DETECTOR
CIRCUIT
DELAY-SEC
MODEL DELAY-SEC
(ZONE)
THE DELAY TIME MARKED ON THE INSTALLED
+
RED
DETECTOR(S) IS TO BE USED
BELL CIRCUIT SUPERVISION JUMPERS
INTACT: Supervised using 2k EOLR
1
CUT: Not supervised (no EOLR used)
BELL 1
BELL 2
Make connections using
4142TR cable (supplied)
W1
W4
(WHITE)
(WHITE)
TRNSFMR
BELL OUTPUTS
AUX. RELAY
1
2
3
4
5
6
7
8
9
10
BELL 1
BELL 2
+
+
BELL
BELL
AUX RELAY (FORM C)
programmable response
+
(not supervised)
HORN
HORN
Contact Rating:
28V, 2.8A
AUXILIARY POWER #1
resistive loads
Rating: 10 - 14VDC
1.0A MAX (STANDBY)
1.7A MAX (ALARM)
2k (Note 2)
2k
See Note 1.
ALARM POLARITY SHOWN
(not supervised)
Each output may be selected for
Style Y supervision or no supervision
(See main PCB jumpers W1, W4 and
zone 970, 971, programming.
FIRE CKTS: Supervise using 2k EOLR.
Use polarized sounding devices.
BURG CKTS: Supervision not req'd.
EOLRs not req'd. May use non
polarized devices.
Ratings: 10 - 14VDC, 1.7A max.
See note 1, see instructions
for compatible devices.
For commercial fire, bell timeout
must be a minimum of 6 minutes.
ALL CIRCUITS ARE POWER LIMITED EXCEPT
THE OUTPUT OF THE POWER TRANSFORMER

VISTA-32FB SUMMARY OF CONNECTIONS

TEST BURGLARY SYSTEM WEEKLY
TYPES OF FIRE SIGNALLING SERVICE:
Manual fire alarm, automatic fire alarm, sprinkler supervisory and waterflow alarm. UL Listed local control (non-coded).
UL Listed central station and remote station protected premises unit when used with 5140DLM back-up dialer module.
Installation limits under jurisdiction of local authority.
Attach 5140DLM module to main PCB shield using
4 standoffs (supplied)
BACK-UP LINE SEIZE
LED (GREEN)
Connect to main PCB
header J3 using ribbon
cable (supplied)
BACK-UP DIALER ON HOOK
VOLTAGE THRESHOLD (BLUE)
INTACT: 25V
CUT: 13V
OPTIONAL 5140DLM BACK-UP DIALER MODULE
MAIN PCB SHIELD
J4 KEYPAD PORT #2
See instr. regarding port #2 use
1. GROUND (to keypad black wire)
KEYPAD PORT #2
4. DATA IN 2 (to keypad green wire)
5. AUX PWR #2 (to keypad red wire)
2 3 4
5
6 7 8
9
J4
Rating: 10 - 14 VDC,
400mA max. See note 1
7. DATA OUT 2 (to keypad yellow wire)
PINS 2, 3, 6, 8 & 9 NOT USED
(not supervised)
KEYPAD PORT #1
ZONE 1
ZONE 2
ZONE 3
11
12
13
14
15
16
17
18
19
+
Red
Blk
Grn Yel
REMOTE KEYPADS:
6139, 6139R
(See Note 3)
+
+
+
SMOKE
SMOKE
N.C.
N.C.
N.C.
N.O.
N.O.
N.O.
2k (Note 2)
2k
2k
ZONE 1-8 NOTES
All zones provide Style B supervision
Zone resistance (excluding EOLR):
- Zones 1, 2, 8: 100 ohms max
- Other zones: 300 ohms max
Zone response: 350 - 500mS (all zones)
J2 VOLTAGE TRIGGERS
See instructions for trigger use and programming
(default functions shown)
The 5140DLM Dialer
1. OUT 4 (SILENT PANIC/DURESS)
Complies with FCC Rules, Part 68
2. OUT 7 (TROUBLE)
FCC Reg. No.: AC398U-68628-MO-N
Ringer Equivalence: 0.7B
3. OUT 3 (BURGLARY/AUDIBLE PANIC)
4. OUT 6 (SUPERVISORY)
BACK-UP PHONE JACK
5. OUT 2 (FIRE)
SEE TELCO
6. OUT 5 (REMOTE KEYPAD SOUNDER)
JACK SHOCK
7. OUT 1 (OPEN/CLOSE)
RJ31X
WARNING
8. GROUND
BELOW
9. IN 1 (N.O. LOOP)
RATINGS: OUT 1, 5, 7:
(connect using supplied cable)
LOW: 2K TO GROUND
Supervision is programmable
HIGH: 10 - 14VDC, 20mA MAX
OTHER OUTS: LOW: 1K TO GROUND
HIGH: 10 - 14VDC THRU 5K
BACK-UP DIALER EARTH
GROUND SCREW
(wire to main PCB
VOLTAGE
terminal #30)
TRIGGERS
(not supervised)
Make connections using
4142TR cable (not supplied)
CONNECTION OF THE FIRE ALARM
SIGNAL TO A FIRE ALARM HEAD-
QUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLY WITH
INTERFACE TO 5140DLM
THE APPROVAL OF THE LOCAL
AUTHORITY HAVING JURISDICTION.
THE BURGLARY ALARM SIGNAL
SHALL NOT BE CONNECTED TO A
POLICE EMERGENCY NUMBER.
ZONE 5
ZONE 6
ZONE 7 ZONE 8
20
21
22
23
24
25
26
27
28
29
ZONE 4
+
+
+
+
+
GLASS
BREAK
N.C.
N.C.
N.C.
N.C.
N.C.
N.O.
N.O.
N.O.
N.O.
N.O.
2k
2k
2k
2k
2k
Ratings for zones 1,2:
- 10 - 14VDC
TO OTHER DEVICES
- 2mA max for smoke det. (up to 16 detectors
Polling Loop Ratings: (supervised)
of the type specified in the instructions
128mA max. See Note 1.
can be used)
See instructions for compatible devices
UL compatibility ID: A
and for max wire run length
Do not mix fire and burg. sensors on one loop.
N.C. contacts for burg. usage only.
The VISTA-32FB Main Dialer
Complies with FCC Rules, Part 68
FCC Reg. No.: AC398U-68192-AL-E
Ringer Equivalence: 0.7B
1
2 3 4
5
6 7 8
9
J2
MAIN DIALER ON HOOK
VOLTAGE THRESHOLD
INTACT:25V
CUT: 13V
W6
(BLUE)
J3
MAIN
Connect
RJ31X using
cable supplied.
RJ31X
Supervision is
30
programmable
PHONE JACK
WARNING:
TO PREVENT
RISK OF
ELECTRICAL
SHOCK,
POLLING
LOOP
DISCONNECT
TELCO JACK
BEFORE
SERVICING
+
THIS PANEL
4209U
EARTH GROUND
See instructions for
proper earth ground
connections
4192SD
SMOKE
4208U