Compatible Polling Loop Devices - ADEMCO VISTA-32FB Installation And Setup Manual

Fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

VISTA-32FB Installation and Set-Up Guide
trigger the dialer. When each zone is restored, the READY TO ARM message should
appear again.
If a zone or zones are not displayed at the correct partition's keypad(s), check both keypad and
zone programming to verify the correct partition assignment.
When the proper displays on the keypad(s) are received, the polling loop zones in the
system are functioning properly.
7. Power down and continue to the next section.
The 4190WH/SN right loop must not be used, and the left loop must be EOLR-supervised.
The 4278 Auxiliary Sensor Loop cannot be used.
U L
The 4297 must be powered from the VISTA-32FB Auxiliary Power Output or from a UL Listed
supplementary power supply.

Compatible Polling Loop Devices

4208U
4208SNF
4190SN
4193SN
4293SN
7–6
8-Zone Expander
Surface mount 2 –
Zone Vplex Serial ID
module
Two-zone SIM Vplex
Serial Interface
Module
Single-zone mini-
SIM Vplex Serial
Interface Module
Accommodates up to 8 class B zones
(4208U)/6 class B + 2 class A zones
(4208SNF) via the polling loop.
DIP switch selectable serial ID #s (4208U
optionally supports dip switch selectable
zone #s).
The first two zones can be either normal or
fast response (DIP switch-selectable).
All zones are EOLR-supervised with a 10k
ohms resistor provided with the unit.
2 zone Vplex Serial ID input module.
Rated for UL Commercial fire applications,
supervised zone.
Serial number preprogrammed, no special
programmer required.
Two-zone SIM, ½"x3/8"x2-3/4".
Rated for UL Commercial fire applications
Serial ID number preprogrammed, no
special programmer required.
Smallest SIM in family, 3/8"x1/4"x1-3/4"
Serial ID number preprogrammed, no
special programmer required.