ADEMCO VISTA-32FB Installation And Setup Manual page 129

Fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

1 17 LOBBY PARTITION
Enter the Common Lobby Partition (1-2).
Enter 0 if none.
1 18 AFFECTS LOBBY (partition-specific)
Enter 1 if this partition affects the common lobby. The system will not arm the lobby
unless this partition is armed already. Also, will cause lobby to disarm when this
partition disarms.
Enter 0 if the partition does not affect the common lobby.
1 19 ARMS LOBBY (partition-specific)
Enter 1 if arming this partition causes the system to attempt to arm the common lobby
partition automatically. Can only arm lobby if all other affecting partitions are armed.
To enable this field, field 1 18 must also be enabled (partition-specific).
Enter 0 if arming this partition will not attempt to arm the common lobby partition.
1 20 EXIT ERROR LOGIC ENABLE
Enter 1 to enable (entry/exit doors and interior points will be bypassed if left open).
Enter 0 if Exit Error Logic is not desired. Must be 0 for UL commercial burglary
installations.
1 21 EXIT DELAY RESET
Enter 1 to reset exit delay to 60 seconds after door is closed.
Enter 0 if exit delay not to be reset. Must be 0 for UL commercial burglary
installations.
1 22 CROSS ZONING PAIR ONE
Enter the first pair of zones, which must both be faulted within a five-minute period of
each other to cause an alarm.
Enter 00,00 to disable. Must be 00,00 for UL burglary installations.
1 23 CROSS ZONING PAIR TWO
Enter the second pair of zones, which must both be faulted within a five-minute period
of each other to cause an alarm.
Enter 00,00 to disable. Must be 00,00 for UL burglary installations.
1 24 CROSS ZONING PAIR THREE
Enter the third pair of zones, which must both be faulted within a five-minute period of
each other to cause an alarm.
Enter 00,00 to disable. Must be 00,00 for UL burglary installations.
1 25 CROSS ZONING PAIR FOUR
Enter the fourth pair of zones, which must both be faulted within a five-minute period of
each other to cause an alarm.
Enter 00,00 to disable. Must be 00,00 for UL burglary installations.
Section 23 – Data Field Descriptions
[00,00]
|
[00,00]
|
[00,00]
|
[00,00]
|
[0]
[0]
[0]
[0]
[0]
|
|
|
|
23–11