Programming The Bell Outputs; Figure 14-1: External Sounder Connections - ADEMCO VISTA-32FB Installation And Setup Manual

Fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

Programming the Bell Outputs

1. Enter Data Field Program Mode [Installer Code] + [8 0 0].
2. Program the following data fields:
08
13
16
1 47
3 57
3 59
3 15
3 60
3. Enter Zone Programming in #93 Menu Mode (refer to the Quick Start Guide) to assign
zones to bell outputs and/or auxiliary relay.
4. Exit Program Mode by pressing 99.
The bell outputs will not respond if zones are not assigned to them. For fire alarms, the system
will display FIRE ALARM SILENCED. This message will also be displayed if the bell output is not
supervised.
(Shows wiring for bell outputs configured using factory default programming selections)
BELL 1 FACTORY DEFAULTS
Bell 1 is configured as a burglary bell circuit
• Use nonpolarized Grade A indicating devices
(e.g., ADEMCO No. AB12 - see below)
• Wiring is not supervised; cut white jumper, W1,
on main PCB
• Activates for zones 3-8 alarms (by default,
zones 3-8 are assigned to burglary partition 1)
• Steady alarm output
• 16 minute timeout
BELL 2 FACTORY DEFAULTS
Bell 2 is configured as a fire bell circuit
• Use polarized indicating devices
• Class B open/short supervision
• 24 hr. trouble response to faults
• Activates for zones 1-2 alarms (by default,
zones 1-2 are assigned to fire partition 3)
• Pulsed alarm output
• No timeout
AB12 BELL/BOX WIRING
1
2
3
4
TAMPER
SWITCHES
BELL

Figure 14-1: External Sounder Connections

Temporal Siren Pulse
Select Timeout for Bell 1
Confirmation of Arming Ding for Bell 1
Enable Chime for Bell 1
Confirmation of Arming Ding for Bell 2
Enable Chime for Bell 2
Select either Steady or Pulsing for each bell circuit output
Select Timeout for Bell 2
3
4
5
-
+
+
BELL 2
BELL 1
2k EOLR
(Model 610-7)
AB12 WIRING NOTES:
• Disconnect the AB12's factory-wired connection
from its terminal #4 to its outer box.
• Set field 3
17 to "1" to enable zone 6 tamper
*
function.
• Assign zone 6 to a burglary partition. Program
it for day trouble/night alarm response (type 05)
when this bell is used by only one burglary
partition. Program it for 24 hr. audible alarm
response (type 07) when this bell is used by
more than one burglary partition.
• All wiring from AB12 to panel must be run in
conduit.
2k EOLR
5
6
AB12 OUTER BOX
INNER LINER
Section 14 – External Sounders