Section 23 - Data Field Descriptions - ADEMCO VISTA-32FB Installation And Setup Manual

Fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
The following is a description of all data fields provided by this control. If you have followed
earlier instructions during the installation of the various devices, many of these fields will
already have been programmed.
If you need more information about actual programming procedures, see Section 20: The
Mechanics of Programming.
00 INSTALLER CODE
The Installer's Code is a 4-digit code reserved for installation company use. This is the
only code that can be used to enter the Program Mode from the keypad. This code
cannot be used to disarm the system if not used to arm the system. This code cannot
reenter Programming Mode if exited by the 98 command.
08 TEMPORAL SIREN PULSE
If either bell is selected for pulsing (program field 3 15), this field will determine the
rhythm and rate of pulsing as follows: If enabled (1), pulse rate will be three dings and
a pause, repeated. If disabled (0), the pulse rate will be 1 sec. on, 1 sec. off.
09 ENTRY DELAY #1 (partition-specific)
Entry delay defines the delay time that allows users to re-enter the premises through a
door that has been programmed as an entry delay door and disarm the system without
sounding an alarm. The system must be disarmed within this period or an alarm will
occur. Enter the entry delay time (01-15 multiplied by 15 seconds or 00 for no delay), up
to a maximum delay of 225 seconds (15 multiplied by 15 seconds), for zones assigned to
Zone Type 01.
10 EXIT DELAY #1 (partition-specific)
Exit delay defines the delay period that allows users to leave the premises through a
door that has been programmed as an entry/exit delay door after arming the system
without setting off the alarm. Enter the exit delay time (01-15 multiplied by 15 seconds
or 00 for no delay), up to a maximum delay of 225 seconds, for zones assigned to Zone
Type 01.
11 ENTRY DELAY #2 (partition-specific)
Entry Delay #2 is used for a secondary door requiring a longer delay than those
assigned to Entry Delay #1. This delay may not exceed 45 seconds for UL commercial
burglary installations.
12 EXIT DELAY #2 (partition-specific)
Exit Delay #2 is used for a secondary door requiring a longer delay than those assigned
to Exit Delay #1. This delay may not exceed 60 seconds for UL commercial burglary
installations.
Data Field Descriptions