ADEMCO VISTA-32FB Installation And Setup Manual page 130

Fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

VISTA-32FB Installation and Set-Up Guide
1 26 PANIC BUTTON OR SPEEDKEY
For each lettered key A-C, enter 00 to assign that key's respective panic function, or
enter a speedkey macro number 01-32 to assign a particular macro to that key. For the
D key, enter 00 to use the D key to select a macro to execute when key is pressed, or
enter a macro number 01-32 to execute a particular macro with the D key.
Instead of the 32 macros, the A, B, and C keys can be programmed for any of 3 other
functions.
Choice 33 = fire sounder silence. The key, when pressed, will silence fire alarms.
Choice 34 = display next fire alarm. The key, when pressed, will display the next fire
alarm present in the system.
Choice 35 = display previous fire alarm. The key, when pressed, will display the
previous fire alarm present in the system.
Note: Choices 34 and 35 should be used in conjunction with field 3 01 Fire Display
Lock.
1 28 RF TX LOW BATTERY SOUND
Enter 0 if audible beep and display upon RF transmitter low battery condition is desired
only in disarmed state.
Enter 1 if audible beep and display is desired in both armed and disarmed states.
Must be 1 for UL.
1 29 RF TX LOW BATTERY REPORTING
Enter 1 if a Trouble message for RF transmitter low battery condition is to be sent to
the central station.
Enter 0 if no report for transmitter low battery is desired. Note that a Trouble message
will be sent for a transmitter supervision failure, independent of this selection.
Must be 1 for UL.
1 30 RF RCVR SUPERVISION CHECK-IN INTERVAL
Enter the check-in monitoring interval in 2-hour increments.
Enter 02-15 times 2 hours (4-30 hours).
Failure of a receiver to receive any RF signal within the time entered will result in
activation of the response type programmed for zone 990 for the first receiver and zone
988 for the second receiver and their related communication reports.
Enter 00 to disable receiver supervision.
Max. 2 (4 hr) for UL.
1 31 RF TRANSMITTER CHECK-IN INTERVAL
Enter the check-in monitoring interval in 2-hour increments.
Enter 02-15 times 2 hours (4-30 hours).
Failure of an individual transmitter to send a supervision signal within the time
entered will result in a trouble response and related communication report. Enter 00 to
disable transmitter supervision.
Max. 2 (4 hr) for UL.
23–12
|
[00,00,00,00]
A
|
|
|
B
C
D
[0]
[0]
[02]
|
[02]
|