Section 21 – Zone Type Definitions
Type 16: Fire With Verification
This zone type is used when smoke alarm verification is desired on hardwire and polling loop zones
containing only 2-wire or 4-wire smoke detectors. An open will initiate a trouble response and a short will
initiate a fire alarm response. Initial short detection causes 7-second smoke detector power reset.
Subsequent short detection within 90 seconds of reset causes fire alarm.
Type 17: Fire Waterflow
An open on this zone causes a trouble response. Shorts that remain present longer than the programmed
time delay (fields 3 16 and 3 18) cause a fire alarm response. This zone can be silenced by pressing [Code]
+ OFF or when the waterflow restores (programmed in field 3 14).
Type 18: Fire Supervisory
This zone type is assigned to a zone having sensors that monitor fire sprinkler systems (i.e., PIV switches,
etc.). A short on this zone causes a supervisory response. Opens can be programmed either for a trouble or a
supervisory response based on the entry in data field 3 13.
Type 19: 24-Hour Trouble
An open or short on this zone type causes a trouble response. No external alarm sounders are activated.
Type 20: Arm-STAY*
This is a special-purpose zone type used with 5800 Series wireless transmitters, which will result in arming
the system in the STAY Mode when the zone is activated.
Type 21: Arm-AWAY*
This is a special-purpose zone type used with 5800 Series wireless transmitters, which will result in arming
the system in the AWAY Mode when the zone is activated.
Type 22: Disarm*
This is a special-purpose zone type used with 5800 Series wireless transmitters, which will result in
disarming the system when the zone is activated.
Type 23: No Alarm Response
This zone type can be used on a zone when an output relay action is desired, but with no accompanying
alarm (e.g., for lobby door access).
* Note that these zone types are for use by 5800 Series devices only!
NOTE FOR PANIC KEYS: Keypad panic zones share the same zone response type for all 2 partitions, but
panics may be individually enabled for each partition.
IMPORTANT! FAULT ANNUNCIATION
Polling loop and RF troubles (zones 988, 990, and 997) will report as trouble conditions only, and as such,
should be assigned zone type 19 if annunciation is desired.
See Polling Loop Supervision in Section 7: 2-
Wire Polling Loop Expansion (Zones 009 – 032) and RF System Operation and Supervision in Section 8:
Wireless Zone Expansion section for more information.
21–3