ADEMCO VISTA-32FB Installation And Setup Manual page 131

Fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

1 33 TOUCH-TONE W/ROTARY BACKUP
Enter 1 to enable rotary backup dialing if communicator is not successful in dialing
using Touch-tone DTMF on first attempt.
Enter 0 if this option is not desired.
1 34 COMM. SPLIT REPORT SELECTION
This field allows certain reports to be directed to either the primary or secondary phone
number.
Enter 0, 1, or 2, in accordance with the following:
0 = split reporting disabled;
1 = Alarm, Alarm Restore and Cancel reports sent to primary telco number, all others to
secondary telco number;
2 = Open/Close and Test reports sent to secondary telco number and all other reports to
primary;
3 = Fire Alarms and Fire Restore reports sent to primary telco number, all reports to
secondary.
See 51 for split/dual reporting combinations.
1 42 CALL WAITING DEFEAT
Enter 1 for the panel to defeat Call Waiting on the first attempt (DO NOT enable unless
Call Waiting is being used).
Otherwise, enter 0.
1 43 PERMANENT KEYPAD DISPLAY BACKLIGHTING (partition-specific)
Enter 1 if backlighting for the keypad display is to remain on at all times.
Enter 0 if the display should remain unlit unless a key is pressed. The backlighting then
turns off again after a period of keypad inactivity. Note that when a key is pressed,
display backlighting turns on for all keypads in that partition.
1 44 WIRELESS KEYPAD TAMPER DETECT
Enter 1 to enable tamper detection on wireless keypad.
Enter 0 if tamper detection is not desired. If more than 40 key depressions are received
without a valid sequence (arm, disarm, etc.), the control panel will disable the wireless
keypad. The inhibit is removed once a valid key sequence is received from a wired
keypad.
1 45 EXIT DELAY SOUNDING (partition-specific)
Enter 1 if beeps from the keypads during exit delay are desired. Enter 0 for no keypad
sound during exit delay.
1 47 CHIME ON BELL 1 (partition-specific)
Enter 1 for chime annunciation using the external alarm sounder. If not desired, enter
0.
Section 23 – Data Field Descriptions
[0]
[0]
[0]
[0]
[0]
[0]
[0]
23–13