VISTA-32FB Installation and Set-Up Guide
Bell Outputs
Provides two style-Y, supervised bell outputs on the control panel itself. A 4204CF Relay
Module can supply two additional style-Y supervised bell outputs.
Auxiliary Relay
Provides a built-in Form C relay that can be used for one of the following:
•
Alarm activation.
•
Trouble/supervisory activation.
•
4-wire smoke detector reset.
•
Battery saving feature (disconnects power from noncritical loads 4 hours after AC power
loss).
Optional Output Relays
Accommodates the use of 16 relay outputs using ADEMCO's 4204 and 4204CF Relay
Modules. Each 4204 module provides four Form C relays for general purpose use. Each
4204CF provides two style-Y supervised bell outputs. Relay outputs have the following
characteristics:
•
Can be programmed to activate in response to system events.
•
Can be programmed to activate using time intervals.
•
Can be used for additional style-Y supervised bell outputs (4204CF only).
•
Can be activated manually using the #70 Relay Command Mode.
•
Can be supervised by control panel (zones 601-616).
•
Can each have an alpha descriptor assigned to it.
Optional VISTA Interactive Phone Module
Supports the ADEMCO 4285/4286 VIP Module. This permits access to the security system
to do the following:
•
Obtain system status information.
•
Arm and disarm security system.
•
Control relays.
The 4285/4286 VIP Module is not Listed for use with the VISTA-32FB Control Panel in a UL
U L
commercial installation .
Optional 24-Volt Power Supply
Compatible with the PS24 Power Supply Module, which supplies two 24VFW, 1.7A full-
wave- rectified, unfiltered outputs. The module is used to supply power to:
•
Alarm notification appliances (sirens, strobes, etc.).
•
Auxiliary devices that can operate using full-wave-rectified, unfiltered voltage.
The optional PS24 Power Supply Module may only be used with the optional VISTA-ULKT
enclosure kit and the optional 1451-24 dual 18VAC/30VAC secondary wired-in transformer. The
PS24 is designed to mount inside the VISTA-ULKT enclosure (either by itself or along with the
VISTA-32FB PC-Board) and is powered from the 1451-24 transformer's 30VAC winding.
1–4