The VISTA-32FB will support the 4100APG and serial printer. See Figure 18-2.
The serial printer must be configured for 1200 baud rate, seven data bits, even parity, and one
stop bit. (7/E/1).
When the module's mounting and wiring is completed, the module's cover should be attached
(with label affixed, as indicated next).

Programming the Control for the Pager

In field 64 enter 1 to enable the 4100APG pager interface.
In field 65 enter the phone number of the paging service for Alarm reports. Up to 17
digits may be entered.
In field 66 enter the Pager ID number of the paging service for Alarm reports. This is
the PIN number. Up to 10 digits may be entered.
In field 67 enter the phone number of the paging service for Trouble reports. Up to 17
digits may be entered.
In field 68 enter the Pager ID number of the paging service for Trouble reports. This is
the PIN number. Up to 10 digits may be entered.
In field 69 enter the phone number of the paging service for Bypass reports. Up to 17
digits may be entered.
J2
11 12
Aux. Pwr
Red
Aux. Gnd
Black
RxD
DTR

Figure 18-2: Wiring the 4100APG With the Serial Printer

Section 18 – 4100APG Pager Interface
4100SM
8
7
6
5
4
3
2
1
DB-25
DB-25
DB-9
Serial Port Input
RJ-11
1200 Baud Serial
Printer 7-E-1
4100APG
Line
T T
o elco
18–3