VISTA-32FB Installation and Set-Up Guide
3 61 AUX RELAY FUNCTION SELECTION
Select the condition that will trigger the auxiliary relay. Options are: 0 =
Trouble/Supervisory; 1 = Alarm, silenced by [Code] + [OFF]; 2 = Smoke detector reset;
3 = Battery save; 4 = Alarm, silenced by [Code] + [#] + [67].
3 82 BURG FEATURES ON PARTITION 1 ENABLE
Enter 1 to enable burglary features on Partition 1.
Enter 0 to disable Arm AWAY, STAY, INSTANT, MAXIMUM, Test, and Chime
functions (burglary features are automatically enabled on other partitions).
3 85 SYSTEM ZONE BYPASS INHIBIT
Enter 0 to prevent bypass of fire and system supervisory zones.
Enter 1 to allow only the Installer Code to bypass.
Enter 2 to allow Installer or Master Code to bypass.
Note: Applies only to fire zone types 9, 16, 17, and 18 and system zones 970-977.
Applies to Partition 1 only.
23–20
[1]
[1]