Figure 3-7: Wiring Auxiliary Relay For Alarm Activation; Figure 3-8: Wiring Auxiliary Relay For Smoke Detector Reset - ADEMCO Vista-32FB Installation And Setup Manual

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for Vista-32FB:
Table of Contents

Advertisement

VISTA-32FB/VISTA-128FB Installation and Setup Guide
If field 3
61 = 4, the auxiliary relay remains activated
until User Code + # + 67 is entered. This option can be
used for elevator recall or ventilator shutdown on fire
alarms. By default, the relay is set to activate on alarm
zones 1-8 with no timeout (field 3
AUX RELAY FACTORY DEFAULTS
ACTIVATES FOR ZONES 1-8 ALARMS
(STEADY ALARM OUTPUT).
NO TIMEOUT.
NOTES:
USE NON-POLARIZED INDICATING DEVICES.
WIRING IS NOT SUPERVISED.
DO NOT EXCEED RATINGS OF THE SUPPLY USED.
IF AUX. PWR. 1 OUTPUT IS USED, THE COMBINED
ALARM CURRENT DRAIN FROM AUX. PWR. 2,
BELL 1, AND BELL 2 CANNOT EXCEED 2.3A MAX.
Trouble/Supervisory Activation
(3
61 = 0) Steady activation in response to any zone or
system related trouble condition or to any fire
supervisory condition. The auxiliary relay remains
activated until all fault conditions have been corrected
and a User Code + OFF is entered.
4-Wire Smoke Detector Reset
(3
61 = 2) Momentary (6-second) activation in response
to a second entry of a User Code + OFF sequence
following a fire alarm condition. This interrupts power
to 4-wire smoke detectors connected to hardwired zones
1-8 and polling loop zones, allowing the detectors to be
reset. Power to the detectors should be wired to the
auxiliary relay and to Aux. Power 1 output, see Figure
3-8.
N.O.
POLE
N.C.
Aux. Pwr 1
10
Keypad Prt 1
CONTROL
PANEL
ZONE
TERMINALS
(15-27)
3-6
61 = 1).

Figure 3-7: Wiring Auxiliary Relay for Alarm Activation

AUXILIARY RELAY
7
+
8
9
+
11
-
12
+
+
-

Figure 3-8: Wiring Auxiliary Relay for Smoke Detector Reset

When field 3
programmed to give a brief activation for confirmation
of arming ding (field 3
ALARM
7
8
+
Battery Saver
(3✳61 = 3) When this option is selected, the auxiliary
relay is normally activated (e.g., N.O. and pole contacts
are connected) and de-activates 4 hours after the start
of AC Loss. Using this feature, non-critical loads, such
as supplementary keypads, can be disconnected from
the auxiliary power outputs, allowing a smaller
capacity battery to be used. The relay re-activates
within a few seconds after the AC power restores.
BLK
4-WIRE SMOKE
DETECTORS
+
-
-
HEAT
DETECTOR
61 = 1, the auxiliary relay can be
57) or Chime Mode (field 3
9
10
11
12
CAN DRAW POWER FROM
AUX. PWR. 1 OUTPUT OR
FROM SEPARATE SUPPLY.
+
EOL
POWER
SUPERVISION
RELAY
MODULE
A77-716B
SHOWN POWERED.
RELAY OPENS WHEN
POWER IS LOST
2000
OHM
EOLR
59).