Remote Keypad Sounder Operation And Wiring; Remote Keyswitch Operation And Wiring; Figure 12-1: J2 Pin Assignments And Functions; Figure 12-2: Remote Keypad Sounder Wiring - ADEMCO VISTA-32FB Installation And Setup Manual

Fire and burglary partitioned security system with scheduling
Table of Contents

Advertisement

VISTA-32FB Installation and Set-Up Guide

Remote Keypad Sounder Operation and Wiring

An optional Amseco PAL 328N Piezo Sounder can be used to duplicate the sounds produced
by the keypad's built-in sounder. The panel will remote all sounds (i.e., alarm, trouble,
chime, entry/exit, etc.) produced by the keypad's built-in sounder except for the short beeps
associated with keypad key depression. One application of this feature might be to produce
chime sounds at a distant location from the panel's keypads. If used, program field 3 20
must be set to 0 (factory default) to enable the remote sounder option, and field 15 must be
set to the desired partition number. The PAL 328N must be connected to J2/OUT 5 as shown
in Figure 12-2.

Remote Keyswitch Operation and Wiring

An optional UL Listed remote keyswitch, such as the ADEMCO 4146, can be used for remote
arming/disarming of the burglary portion of the system and for remotely silencing alarms. If
used, the following must be programmed:
12–2
J2 CONNECTOR
1
2
3
4
5
6
7
8
MAKE CONNECTIONS USING 4142TR (1 SUPPLIED)

Figure 12-1: J2 Pin Assignments and Functions

Figure 12-2: Remote Keypad Sounder Wiring

9
FIELD 3*19 = 0
FIELD 3*20 = 0
(DEFAULT)
INPUT 1
LORRA
XMIT OKAY
GROUND
OUT 1
OPEN/CLOSE
OUT 5
REMOTE
CONSOLE SOUNDER
OUT 2
FIRE ALARM
OUT 6
FIRE
SUPERVISORY
OUT 3
BURGLARY
ALARM
OUT 7
TROUBLE
OUT 4
PANIC ALARM
J2 CONNECTOR
1
2
3
4
5
6
7
8
9
4142TR CABLE
FIELD 3*19 = 0
FIELD 3*19 = 0
FIELD 3*20 = 1
FIELD 3*20 = 2
LORRA
LORRA
XMIT OKAY
XMIT OKAY
KEYSWITCH
5140LED
ARMED LED
AC FAIL LED
KEYSWITCH
5140LED
READY LED
DIALER 2 FAIL LED
FIRE ALARM
FIRE ALARM
FIRE
FIRE
SUPERVISORY
SUPERVISORY
BURGLARY
5140LED
ALARM
COMM FAIL LED
TROUBLE
TROUBLE
PANIC ALARM
5140LED
DIALER 1 FAIL LED
BLACK
AMSECO PAL-328N
PIEZO SOUNDER
(10MA)
+
RED
FIELD 3*19 = 1
PRINTER DTR
AS SELECTED
IN FIELD 3*20
AS SELECTED
IN FIELD 3*20
PRINTER RXD
AS SELECTED
IN FIELD 3*20
AS SELECTED
IN FIELD 3*20
AS SELECTED
IN FIELD 3*20
AS SELECTED
IN FIELD 3*20

Hide quick links: